NEMA B Three Phase Squirrel Cage motors – Locked Rotor Current
The National Electrical Manufacturers Association has defined different torque profiles for three phase induction motors. For example, design D offers high starting torque and might be advantageous in a drill or press application.
By far, the most common squirrel cage motor design is NEMA B which strikes a compromise between moderate starting torque and low slip speed (< 5% of at rated load).
For NEMA B motors, here is a listing of the maximum allowed locked-rotor current at 230V, as defined by MG 1 12.35.1. For values outside 230V, NEMA states “The locked-rotor current of motors designed for voltages other than 230 volts shall be inversely proportional to the voltages”. Which leads us to calculate the other values.
Locked rotor current (A) | ||||
---|---|---|---|---|
Rated voltage | ||||
HP | 200 | 230 | 460 | 575 |
0.5 | 23 | 20 | 10 | 8 |
0.75 | 29 | 25 | 13 | 10 |
1 | 35 | 30 | 15 | 12 |
1.5 | 46 | 40 | 20 | 16 |
2 | 58 | 50 | 25 | 20 |
3 | 74 | 64 | 32 | 26 |
5 | 106 | 92 | 46 | 37 |
7.5 | 146 | 127 | 64 | 51 |
10 | 186 | 162 | 81 | 65 |
15 | 267 | 232 | 116 | 93 |
20 | 334 | 290 | 145 | 116 |
25 | 420 | 365 | 183 | 146 |
30 | 500 | 435 | 218 | 174 |
40 | 667 | 580 | 290 | 232 |
50 | 834 | 725 | 363 | 290 |
60 | 1001 | 870 | 435 | 348 |
75 | 1248 | 1085 | 543 | 434 |
100 | 1668 | 1450 | 725 | 580 |
125 | 2087 | 1815 | 908 | 726 |
150 | 2496 | 2170 | 1085 | 868 |
200 | 3335 | 2900 | 1450 | 1160 |
250 | 4198 | 3650 | 1825 | 1460 |
300 | 5060 | 4400 | 2200 | 1760 |
350 | 5865 | 5100 | 2550 | 2040 |
400 | 6670 | 5800 | 2900 | 2320 |
450 | 7475 | 6500 | 3250 | 2600 |
500 | 8338 | 7250 | 3625 | 2900 |